Grundfos DDA Pumps

Spare Parts for DDA Range Pumps

This page lists replacement and compatible spare parts for Grundfos pumps.
Pump Spares Direct is an independent supplier and is not affiliated with, endorsed by, or authorised by Grundfos.

Image shown for pump identification purposes only.

DOWNLOAD DATASHEET

Product Summary

Genuine and compatible spare parts for the Grundfos SMART Digital DDA stepper-driven diaphragm dosing pump, used across Australia for chlorination and disinfection, pH correction, coagulant and chemical dosing in water and wastewater treatment. Every DDA from the 7.5 l/h DDA 7.5-16 to the 200 l/h DDA 200-4 uses the same dosing head build (diaphragm, suction and discharge valves, deaeration valve), so tick what you need and we’ll match the exact kit to your nameplate (e.g. DDA 12-10 AR-PV/T/C-F-31U2U2IG).

Type: Stepper-motor diaphragm dosing pump Build: PVDF or PVC dosing head (PP, SS to order) Range: DDA 7.5-16 – DDA 200-4 · 7.5–200 l/h · to 16 bar

Spare Parts List

✓ Tick the parts you need. Grundfos SMART Digital kits are matched to the dosing head material and pump size, so your nameplate model is all we need to get them right. Not sure which items? Add a photo of the nameplate and we’ll work out the kit for you.

SelectWear / Service ItemFunction & when to replace
Common Service Kits
Spare Parts KitThe standard service kit: suction and discharge valves, diaphragm and O-rings, matched to your head material, gasket and valve ball codes. Fit it at the routine service interval or whenever output drops off.
Diaphragm KitReplacement diaphragm sized to your pump (44 to 117 mm across the range). Replace after a diaphragm leak alarm or at the service interval.
Valve KitComplete suction and discharge valves with balls, seats and seals, standard or spring-loaded. The usual fix for lost prime, back-flow or inaccurate dosing.
Complete Dosing HeadFully assembled dosing head for your model, with valves, diaphragm and deaeration valve. The quickest fix for a cracked, chemically attacked or heavily scaled head.
Deaeration ValveManual deaeration (vent) valve for priming and releasing gas from the head, with its return line connection. Replace if it weeps or will not seal.
Other Core Parts
Injection UnitSpring-loaded injection unit at the dosing point, keeping chemical from back-flowing and holding a small counter pressure. Replace if scaled, blocked or leaking.
Foot ValveFoot valve with strainer for the end of the suction line, available with low-level and empty-tank sensing for AR and FCM pumps.
Suction / Discharge TubingSuction, discharge and deaeration tubing sized to your pump connections (e.g. 4/6, 6/9, 9/12 or 19/27 mm).
Pressure Relief / Loading ValvePressure relief valve to protect the pump and line from over-pressure, or a pressure loading valve to hold a steady counter pressure and stop siphoning.
Pulsation DamperSmooths the discharge flow on longer lines or where a steady flow is needed, and reduces pressure peaks on the pump.
Connection Kit / InlaysUnion nuts, hose or pipe inlays and clamps for the pump inlet and outlet, matched to your connection code.
Signal & Power CablesLevel input, pulse/analogue, relay output and mains cables with the correct M12 plugs for SMART Digital pumps.
Complete Replacement PumpWhen a repair doesn’t stack up, we quote a like-for-like SMART Digital DDA from the model on your nameplate.

How we confirm the exact part: SMART Digital DDA kits depend on pump size, dosing head material, gasket, valve ball and valve type. Your nameplate carries all of it in the type key (e.g. DDA 12-10 AR-PV/T/C-F-31U2U2IG: PV = PVDF head, T = PTFE gaskets, C = ceramic balls, 1 = standard valves, 2 = spring-loaded). Tick the items above and add a nameplate photo, and we’ll confirm the correct part and price for your exact pump.

Models

Spare parts are available for every SMART Digital DDA size in the current Grundfos Australia range. The first number on your nameplate (e.g. DDA 12-10) is the maximum flow in l/h; the second is the maximum pressure in bar.

DDA 7.5-16DDA 12-10DDA 17-7DDA 30-4DDA 60-10DDA 120-7DDA 200-4

Models & Key Specifications

ModelMax flow (l/h)Max pressure (bar)Diaphragm (mm)Dosing head (AU range)
DDA 7.5-167.51644PVDF
DDA 12-10121050PVDF or PVC
DDA 17-717750PVDF
DDA 30-430474PVDF or PVC
DDA 60-10601074PVDF or PVC
DDA 120-7120797PVDF or PVC
DDA 200-42004117PVDF or PVC

Control variants AR (alarm relay, pulse, 0/4–20 mA, batch and timer modes) and FCM (AR plus FlowControl). PVDF heads with PTFE gaskets and ceramic balls; PVC heads with EPDM gaskets and spring-loaded valves; PVC heads limited to 10 bar. DDA 7.5–30 (SMART Digital S): G5/8 connections, liquid −10 to +45 °C. DDA 60–200 (SMART Digital XL): G5/4 connections, liquid 0 to +50 °C (PVC +40 °C). 100–240 V, IP65.

Troubleshooting

Pump runs but does not dose

Likely cause: air in the dosing head, a dry or blocked foot valve, worn or dirty suction/discharge valves, or a blocked injection unit. Action: open the deaeration valve and prime the pump; clean the foot valve strainer; check the injection unit for scale or crystallised chemical; if output does not return, fit the valve kit.

Air lock or gassing (sodium hypochlorite, peroxide)

Likely cause: outgassing chemical collecting in the dosing head, often worse with long or warm suction lines. Action: keep the suction line short and below the tank where possible, use the deaeration valve with a return line to the tank, and fit spring-loaded valves for gassing media. The DDA’s auto-deaeration and SlowMode settings also help with gassing liquids.

Diaphragm leak alarm or chemical at the drain hole

Likely cause: a ruptured or fatigued diaphragm. Action: isolate the pump, flush the dosing head and replace the diaphragm, or fit the full spare parts kit. Do not keep running: chemical can reach the drive behind the diaphragm.

Pressure alarm or pump stops on high pressure

Likely cause: a closed or blocked discharge line, a seized injection unit, or a system pressure above the pump rating. Action: check discharge valves are open, clean or replace the injection unit, and confirm the counter pressure suits the model (PVC heads are limited to 10 bar). Fit a pressure relief valve if one is missing.

Dosing rate inaccurate or drifting

Likely cause: worn valve balls and seats, too little pressure difference across the head (a pressure loading valve may be needed), siphoning, or a calibration that no longer matches site conditions. Action: fit the valve kit, check the pressure differential and recalibrate the pump.

Leaking at the dosing head or connections

Likely cause: loose dosing head screws, perished O-rings, or connection nuts and inlays damaged by over-tightening. Action: fit the spare parts kit (valves, diaphragm and O-rings), torque the head screws evenly and replace damaged connection parts.

Display dark, no power or motor fault alarm

Likely cause: supply fault, a damaged mains or signal cable, or a fault in the drive or electronics. Action: check the supply and cables; note any alarm shown on the display. A drive or electronics fault usually means a replacement drive or pump, so send us the nameplate model and alarm details.

Request for Quotation

Selected Parts:

  • No parts selected

Not sure which parts? Just send a photo of the nameplate or part below.

Your pump

Please select your pump model (or choose “Not sure”)

Your details

Please enter your full name
Please enter a valid email address
Please enter a valid phone number

Your enquiry

Please select what you need

Drag & drop image here or tap to browse

JPG, PNG or PDF, max 5MB

File must be smaller than 5MB

Delivery

Please select when you need it
Please enter the delivery suburb or town
Please enter a 4-digit postcode
Postcode and state don't match - please check
Please select a state
Please select a delivery type

We use these details only to prepare and follow up your quote. See our Privacy Policy.

We aim to respond within one business day