Grundfos NBG Pumps

Spare Parts for NBG Range Pumps

This page lists replacement and compatible spare parts for Grundfos pumps.
Pump Spares Direct is an independent supplier and is not affiliated with, endorsed by, or authorised by Grundfos.

Image shown for pump identification purposes only.

DOWNLOAD DATASHEET

Product Summary

Genuine and compatible spare parts for the Grundfos NBG close-coupled end-suction pump (ISO 2858), used across Australia for HVAC chilled and condenser water, heating, water supply, industrial transfer and process duties. Every NBG from the NBG 50-32-160 to the 200 kW NBG 150-125 shares the same build (single impeller, replaceable wear rings, mechanical shaft seal and standard motor), so tick what you need and we’ll match the exact kit to your nameplate (e.g. NBG 100-65-200/198).

Type: Single-stage end-suction, close-coupled Build: Cast iron or 316 stainless, 316 shaft, bronze or stainless wear rings Range: NBG 50-32 – NBG 200-150 · 0.55–200 kW · PN16

Spare Parts List

✓ Tick the parts you need. Grundfos NBG service kits are matched to pump size, impeller diameter, materials and shaft seal code, so your nameplate model is all we need to get them right. Not sure which items? Add a photo of the nameplate and we’ll work out the kit for you.

SelectWear / Service ItemFunction & when to replace
Common Service Kits
Shaft Seal KitMechanical shaft seal with its fitting parts, matched to your seal code (standard BQQE: rubber bellows, SiC/SiC, EPDM; cartridge, tandem and back-to-back seals to order). Replace at the first sign of leakage behind the impeller.
Impeller KitImpeller in cast iron or 316 stainless, trimmed to your diameter (e.g. /198), with its key, nut and washer. Replace if eroded, cracked or out of balance.
Wear Ring KitReplaceable wear rings (bronze on cast iron pumps, duplex stainless on stainless pumps) that seal the impeller eye. Worn rings cost flow and head; renew them at any rebuild.
O-ring & Gasket KitThe O-ring between pump housing and cover plus plug seals, in EPDM or FKM. Renew whenever the pump is opened.
Shaft KitAISI 316 stainless pump shaft for your motor frame and pump size. Replace if scored at the seal seat, bent or worn at the impeller fit.
Other Core Parts
Replacement MotorStandard IE3 motor matched to your kW, frame and speed (2-pole 2900 rpm or 4-pole 1450 rpm), from 0.55 to 200 kW across the range.
Pump HousingVolute casing in cast iron or 316 stainless with inlet and outlet flanges, matched to your pump size. Replace if cracked, badly corroded or eroded.
Pump Cover & Motor StoolThe cover and adapter that join the pump end to the motor and house the shaft seal. Replace if cracked or damaged at the seal seat.
Base PlateSteel base frame for floor mounting, supplied with or added to the larger NBG sizes. We match it to your pump and motor frame.
Complete Replacement PumpWhen a rebuild doesn’t stack up, we quote a like-for-like NBG from the model on your nameplate.

How we confirm the exact part: Grundfos NBG kits depend on pump size, impeller diameter, material version (cast iron, stainless or super vortex), shaft seal code and motor frame. Your nameplate carries all of it, in the model (e.g. NBG 100-65-200/198 A-F-A-BQQE) and the product number. Tick the items above and add a nameplate photo, and we’ll confirm the correct part and price for your exact pump.

Models

Spare parts are available for every NBG size in the current Grundfos Australia range, including the 316 stainless and super vortex versions. In the model (e.g. NBG 100-65-200/198), 100 and 65 are the inlet and outlet sizes (DN), 200 the nominal impeller diameter and 198 the actual impeller diameter in mm.

NBG 50-32-160NBG 50-32-200NBG 65-40-200NBG 65-40-250NBG 65-40-315NBG 65-50-160NBG 80-50-200NBG 80-50-250NBG 80-50-315NBG 80-65-160NBG 100-65-200NBG 100-65-250NBG 100-65-315NBG 100-80-160NBG 125-80-160NBG 125-80-200NBG 125-80-250NBG 125-80-315NBG 125-80-400NBG 125-100-160NBG 125-100-200NBG 125-100-250NBG 125-100-315NBG 125-100-400NBG 150-125-200NBG 150-125-250NBG 150-125-315NBG 150-125-400NBG 150-125-500NBG 200-150-200NBG 200-150-250NBG 200-150-315NBG 200-150-400

Models & Key Specifications

Size (in-out)Casing sizesConnections (in / out)2-pole kW (2900 rpm)4-pole kW (1450 rpm)
NBG 50-32160, 200DN50 / DN321.5–110.55–1.5
NBG 65-40200, 250, 315DN65 / DN405.5–450.75–5.5
NBG 65-50160DN65 / DN504–110.55–1.1
NBG 80-50200, 250, 315DN80 / DN5011–551.1–11
NBG 80-65160DN80 / DN655.5–150.55–2.2
NBG 100-65200, 250, 315DN100 / DN6511–1101.5–15
NBG 100-80160DN100 / DN807.5–18.50.75–2.2
NBG 125-80160, 200, 250, 315, 400DN125 / DN8011–1321.5–45
NBG 125-100160, 200, 250, 315, 400DN125 / DN10018.5–1321.5–55
NBG 150-125200, 250, 315, 400, 500DN150 / DN12545–2005.5–160
NBG 200-150200, 250, 315, 400DN200 / DN15075–1107.5–160

All sizes: liquid temperature −25 °C to +120 °C (clean water / glycol), PN16, standard shaft seal BQQE (others on request), IE3 IP55 motors, 50 Hz. Cast iron versions: cast iron or 316 impeller, 316 shaft, bronze wear rings, AS 2129 Table E flanges. Stainless versions: CF8M (1.4408) housing and impeller, duplex wear rings, DIN PN16 flanges. Super vortex versions (4-pole) pass solids and fibres up to 25 mm.

Troubleshooting

Pump will not start

Likely cause: no supply, a tripped motor protection or fuse, or a seized pump. Action: check the supply and reset the protection; with the power isolated, turn the shaft by hand. A pump that won’t turn needs inspection of the impeller, wear rings and seal.

Motor protection trips repeatedly

Likely cause: overload from running well right of the duty curve (low system resistance), a rubbing impeller, failing bearings or a phase fault. Action: check the voltage on all phases and the motor current; throttle to the duty point; inspect the impeller and bearings; confirm the impeller diameter suits the duty.

Low flow or head

Likely cause: worn wear rings or impeller, air in the pump, a blocked suction strainer or impeller, wrong rotation. Action: vent the pump and check the suction side; clean the strainer and impeller; confirm rotation; if output still falls short, replace the wear ring kit and impeller kit.

Noise or vibration

Likely cause: cavitation (insufficient NPSH), air in the pump, a damaged or out-of-balance impeller, worn bearings, or pipe strain on the flanges. Action: check suction pressure and NPSH; vent the pump; inspect the impeller and bearings; support the pipework so the pump isn’t carrying it.

Leaking at the shaft seal

Likely cause: worn or damaged seal faces, often from dry running, abrasive particles or a seal material that doesn’t suit the liquid. Action: replace the shaft seal kit and renew the O-rings. Never run a NBG dry: the seal relies on the pumped liquid for cooling and lubrication.

Leaking at the pump housing

Likely cause: a perished O-ring between the pump housing and cover, a failed flange gasket, or a cracked housing. Action: fit the O-ring and gasket kit and tighten the housing bolts evenly to Grundfos specification; replace the housing if it is cracked.

Pump runs backwards after stopping

Likely cause: a leaking or missing non-return valve on the discharge. Action: repair or replace the non-return valve. Reverse spin can damage the seal and loosen the impeller.

Request for Quotation

Selected Parts:

  • No parts selected

Not sure which parts? Just send a photo of the nameplate or part below.

Your pump

Please select your pump size (or choose “Not sure”)

Your details

Please enter your full name
Please enter a valid email address
Please enter a valid phone number

Your enquiry

Please select what you need

Drag & drop image here or tap to browse

JPG, PNG or PDF, max 5MB

File must be smaller than 5MB

Delivery

Please select when you need it
Please enter the delivery suburb or town
Please enter a 4-digit postcode
Postcode and state don't match - please check
Please select a state
Please select a delivery type

We use these details only to prepare and follow up your quote. See our Privacy Policy.

We aim to respond within one business day